Other Installation Specification

External Control

Use an external device or a mechanical contract to interlock

and control the ventilation system. The figure below shows the

configuration where one external controller and a kitchen hood or

differential pressure switch are connected.

Using external controller

– It connects both sides of EXT1.

– If the external controller 1 is set to ON position, ERV is

operated in the last used condition.

Using a kitchen hood

– Connect the kitchen hood to both sides of HOOD.

– Set SEG17 of the installation option 1 (02 mode) to 0.

(Default: 1)

– When the kitchen hood is turned on, the supply air operates

at the Turbo fan speed and the exhaust air operates at the

Low fan speed.

Using a differential pressure switch

-Connect the differential pressure switch to both sides of

HOOD.

– Set SEG17 of the installation option 1 (02 mode) to 1.

(Default: 1)

-The pressure difference between the front and back of the

filter is measured to display filter-cleaning reminders on the

wired remote control display.